top of page

Fire Batt

fire_batt 01_uKo3.jpg
fire_batt 02_tVck.jpg

Fill Up And Reinstate The Fire Rating On The Non-Load Bearing Void Slab And Vertical Wall

Fire batt and fire barrier sealant are designed to prevent the passage of fire between compartment walls and floors whilst still allowing for the easy installation of services. The product is tested to BS 476 part 20/ 22 giving a fire and smoke barrier for 4 hours.

At normal temperatures, the fire batt installed with sealant remains flexible to permit thermal and mechanical movement of the services. Both products are unaffected by oil, fungus, moisture, vermin, weather and contain no halogens or asbestos. COAT BACK OF SERVCES IS NOTE REQUIRED.

The advantages of the fire batt and sealant are:

1. Suitable for indoor and outdoor use without additional environmental protection

2. Remains flexible between - 5°C to + 70°C

3. Easy to use fibre free sealant

4. Standard 60mm batt gives 4 hours fire and smoke barrier

5. Long life and easy to use

6. Acoustic isolation

7. Suitable for large openings in walls and floors with additional supports

 

Compliance: 

The product is manufactured in the EU, meeting the highest quality standard in compliance with ISO EN 9001. For fire test information please contact our technical department.

 

Specification: 

Dimensions:

T1200D – 1200mm x 600mm x 60mm

T960D – 900mm x 600mm x 60mm

 

Mineral Fibre Density:

3 180Kg/m³

 

Coating Thickness:

2mm Nominal, 2. 50Kg/m²

 

Fire Resistance:

4 hours BS 476 part 20

 

Insulation:

120 minutes on seal face, 84 minutes on services

 

Thermal Conductivity ( U Value):

0. 35 W/ K for 60mm Board

 

Heat Aging - 336 hrs:

No defects at 40°C

 

Water Vapour Permeability:

3. 08g / m2 / 24 hours

 

Artificial Weathering - 1000 hrs:

No defects – BS3900: F3

 

Acoustic Performance:

34. 7dB at 100Hz to 59. 5dB at 5000Hz

( 60mm Batt only)

44dB mean reduction

 

Maximum Size of Seal:

2 Wall 5. 76M2, Floor 2. 88M

bottom of page